Interlogix VEREX Director User Manual

Page 280

Advertising
background image

272

Verex Director V4.9.1 User's Guide

21-0381E v4.9.1

taken from the corresponding pseudo points. AC
Failure and Battery trouble outputs follow these inputs.

Note: The XL Panel firmware ≥ 4.58g is required.

- Level: The arming levels of the area
assigned to the point for which the point will be fully
monitored by the system.
Exception: For keyswitch operation, see the previous
"Keyswitch" note.
Activity Monitor: The arming levels of the input
point's area for which the point will be treated as an
activity monitor versus a standard sensor (e.g.,
Burglary).

- Class: The basic classification for the point /

sensor (this is referenced in messages
transmitted to the monitoring station);

For Command Points: These are fixed as
'Supervisory'. As well, other than issuing the specific
action, command-points are monitored only for
'Tamper' conditions.

-------------------------

- Bypassable: Whether or not the point can be

bypassed (by a user with 'bypass' authority)
should the need arise (e.g., to allow arming an
area with a broken window, faulty sensor, etc.).

- Chime: Whether or not three short beeps will be

signalled at keypads in the area assigned to this
point whenever the point is triggered (this can
be ‘toggled’ off at a keypad by pressing ƒ5);

Exception: For keyswitch operation, see the previous
"Keyswitch" note.

- Pre-Alarm Warning: For associated input-

points, alarm transmission (to the central
station) will be delayed as per the "Pre-Alarm
Delay" setting (for the specific 'area'). During
the delay, keypad sonalert(s) will be sounded,
giving an authorized user time to "Silence" the
alarm at a keypad. (Selecting "Verify User" will
cancel the alarm transmission.)

Siren Time: To allow a pre-alarm warning to occur,
the siren time for the panel must be greater than 30
seconds. (Siren Time appears under:
Configuration, System, Standard )
For details on setting the "Pre-alarm Delay" time, refer
to "Areas and Related Settings".
To assign an area to be monitored by a specific
keypad, refer to "Expansion Modules".
For Command Points: This selection does not apply
to command points (do not select 'Pre-Alarm Warning'
for command points).

Transmit

- Off / Stay / On: The (applicable area’s) arming

levels for which an alarm message will be

transmitted to the monitoring station whenever
the point is triggered;

For Command Points: Other than issuing the specific
action, command-points are monitored only for
'Tamper' conditions.

Sonalert

- Off / Stay / On: The (applicable area’s) arming

levels for which keypad sonalerts will be
sounded for 1 second when the point is
triggered;

Siren

- Off / Stay / On: The (applicable area’s) arming

levels for which siren outputs will be sounded
when the point is triggered. (The “Siren Time” is
set through the

System

screen.)

For Command Points: Other than issuing the specific
action, command-points are monitored only for
'Tamper' conditions. So, the Transmit, Sonalert, and
Siren selections will take effect only for tamper
conditions.