Installing and connecting a third-party pftu – Nortel Networks 1000E User Manual

Page 443

Advertising
background image

Installing and cross-connecting a Power Fail Transfer Unit

Page 443 of 466

Communication Server 1000E

Installation and Commissioning

Installing and connecting a third-party PFTU

Follow the equipment manufacturer’s instructions for installing the PFTU.
Use the information in Table 59 to connect a third-party PFTU.

Note 1: Refer to Figure 180 on

page 440

to see where the Auxiliary

cable connects to the CS 1000E system.

Note 2: If power is removed from the QUA6, a transfer of the PFTU can
occur.

Table 59
PFTU control lead signals

Lead State

NTAK1104 AUX
cable lead

When PFTU is in
non-transferred state

When PFTU is in
transferred state

BRTN

GROUND

GROUND

BRTN

GROUND

GROUND

-48V AUX

-48V DC (250 mA max.)

-48V DC (250 mA max.)

PFTS

OPEN

GROUND