Step 6 wire aux inputs – YSI 5200A User Manual

Page 25

Advertising
background image

YSI 5200A
48

YSI 5200A
49

Note:

Contactor must meet the electrical requirements of the load.

-

Blower

X

Contactor

Contacts

Coil

YSI 5200A contactor wiring

Power for Blower

Power for Contactor

Switched Power

wire contactor power to “C” pin
wire second wire to “NC”/”NO” as required for application

Figure 3.20

Test Relay Outputs

Apply power to 5200A. Verify device activates at relay test. See Relay Test - page

123.

Note:

Entering the relay test menu turns off any active relays and disables any sensor,

aux, and timer system relays from energizing regardless of the value or condition.

Systems are not reset when the Relay Test menu is exited. To reset the systems after

exiting the Relay Test menu, power cycle the 5200A.

Step 6 Wire Aux Inputs

The 5200A has two auxiliary (aux) inputs. Aux inputs can be used for digital (open/

closed dry contacts) or analog (0-1VDC, 0-5VDC , or 4-20mA) inputs. Aux inputs

can be used for a variety of applications including: level switch, pressure switch,

and/or an external instrument with an analog recorder output. Aux input wires are

terminated at location K - figure 3.21. (See 5200A I/O board wiring diagram on

Installation and Wiring

Installation and Wiring

inside of front panel for identification of aux system number and pin position.) See

Digital Input example - figure 3.22 and Analog Input example - figure 3.23.

Notes:

All aux inputs have input protection, the maximum input voltage should

-

not exceed 6 VDC.

Analog systems will not monitor and/or alarm properly if the device that is

-

installed and configured operates outside the configured analog range.

For proper digital input operation, use low impedance switches and wir-

-

ing. The total resistance should not exceed 200 Ω (ohms).

Directions to Wire Aux Inputs

WARNING: Disconnect external power to the unit before wiring.

AVERTISSEMENT : déconnectez l’alimentation externe de l’unité avant

d’effectuer un câblage quelconque.

Perform steps 1 - 4 of 5200A installation.

1.

Open front panel -

2.

page 39 .

Feed aux device wires through drilled hole in rubber grommet to locations

3.

K.

Terminal strip is removable.

CAUTION:

Run high and low voltage cables through separate bulkhead and

conduit.

Use (1) or (2) pin to terminate one wire and (G) to terminate ground wire.

4.

(G) pin is the common ground for Aux 1 and 2.

CAUTION

: Aux inputs are not isolated. Devices connected must be electrically

isolated from ground and the water.