master

Testing network configurations

slave

master

slave

slave

slave

-represents wired network termination strip

-terminal strips that appear within master/slave box represent terminal strips that are physically

connected to device

-terminal strips that appear outside slave box represent terminal strips not connected to device

When master is first physical device on network, as shown above, connect terminal strip to master and last

slave (slave 4) to begin network testing. Terminal strips for slaves located between the master and the last

slave are then connected, one, by one beginning with slave device furthest from master and continuing to

slave devices closest to master. Testing in the above graphic would occur first with slave 4, then slave 3,

then slave 2, ending with slave 1.

slave

slave

slave

slave

-represents wired network termination strip

-terminal strips that appear within master/slave box represent terminal strips that are physically

connected to device

-terminal strips that appear outside slave box represent terminal strips not connected to device

When master is not the first physical device on network, as shown above, connect terminal strip to master

and outer most slaves (slaves 1 and 4) to begin network testing. Testing in above graphic would occur first

with slaves 1 and 4, and then continuing by testing slave device 2, or slave device 3 until all network

wiring is tested.

Use below network wiring testing method when master is not first physical device on network.

Use below network wiring testing method when master is first physical device on network.

Follow wiring instructions below to avoid testing network wiring with stubs.

1

2

3

4

1

2

3

4

Figure 3.27

Close front panel -

7.

page 40.

5200A networks must be configured point-to-point (instrument-to-instrument).

Network wiring cannot contain loops, stars, or stubs - figure 3.28.

Installation and Wiring

Network configurations

Master

Master

Master

slave

slave

slave

slave

slave

slave

slave

slave

slave

slave

slave

slave

slave

slave

slave

do not wire “star” network

follow master/slave wiring directions figure 3.26

Master

slave

slave

slave

slave

do not wire “loop” network

b

b

good

good

bad

bad

Figure 3.28

Test Network Wiring and Configuration

Apply power to only the master and last slave device on the network. If the master

is not the first physical device on the network, apply power to the master and the

first and last physical slave devices on the network. See Network beginning on

page 93.

Step 8 Wire Communication Equipment

Communication equipment must be installed in order to communicate, either locally

or remotely, with the 5200A. The communication connection can be made locally

(RS232) or remotely with a serial to ethernet device. Only one connection method

can be used at a time. AquaManager supports both connection methods.

Installation and Wiring