Event logging clear logs – YSI 5200A User Manual

Page 53

Advertising
background image

YSI 5200A
104

YSI 5200A
105

In the above sensor log screen shot ORP is disabled.

Event Logging

Menus → System → Data Logging → Event Logging

Control, Alarm, and Timer relays assigned to 5400 systems create events when they

turn on and off. In addition, AC power failures, ethernet device error messages,

and slave network failures are create events. These events are stored in the Event

Log. Event logs identify the 5200A system, are time and date stamped, and record

relay the action (“on” or “off”).

Enter Event Logging menu

1.

Menus → System → Data Logging → Event Logging

Use

2.

and

to scroll and highlight submenus.

Press

3.

to select.

Press

4.

to turn off or on.

Press

5.

to save configuration and return to Run Screen.

Press

to view the 25 most recent event logs.

Press

to view active (“on”) non timer events. See Control Menu - page158

for additional information.

Notes:

The General Alarm does not create an event log whether a general alarm

-

relay is enabled or not.

- Events are not recorded when relays de-energize due to systemwide events.

Systemwide events include: calibration, Svr Hold, factory resets, power

cycle, 30 second sensor system reset, relay test, and disabling systems.

Event logs record the default system name and not the user configured

-

system name.

Configuring the 5200A

Event logs do not record relay number or user configured relay name.

-

Aux analog (non temperature) events will always display “alarm” regard-

-

less if alarms are enabled, see below screen shot on left.

Aux digital events will never display “alarm” regardless if alarms are

-

enabled, see below screen shot on right.

Clear Logs

Menus → System → Data Logging → Clear Logs

Use the Clear Log option to permanently delete all event and/or sensor log records

from the 5200A.

Before permanently deleting sensor and event logs, poll all data using AquaManager.

AquaManager will store all logs to a database in PC database.

Enter Clear Log menu

1.

Menus → System → Data Logging → Clear Logs

Use

2.

and

to scroll submenu.

Press

3.

to select.

The instrument will prompt, “Are You Sure?” Press one of the following

4.

softkeys to confirm:

.

Selecting “Yes” automatically deletes logs and then returns to the Run

5.

Screen after approximately three seconds.

Selecting “No” or “Cancel” does not delete logs and returns to the Data

6.

Logging menu.