YSI 5200A User Manual

Page 51

Advertising
background image

YSI 5200A
100

YSI 5200A
101

Analog 0-1VDC and 0-5VDC and 4-20 mA

Menus → System → Configure Aux →Aux 1-2→Input Type

→0-1V

→0-5V

→4/20mA

Select the analog input type based on the signal being sent from the device.

Notes:

It is normal to hear an on-board relay “click” when switching to or from

-

the 4-20mA aux input type.

Analog systems will not monitor, control, or alarm properly if a device

-

that operates outside the configured analog range is installed and con-

figured.

Suffix

Menus → System → Configure Aux →Aux 1-2→Suffix

Enter the Suffix (up to 4 characters) to describe the input type or units. The suffix

is displayed at the Run Screen. The suffix is typically used to describe the input

signal type.

Example - when using a total dissolved gas pressure sensor, “mmHg” could be used

as a suffix for measuring TGP (total dissolved gas pressure) - figure 4.6, page 101.

Min and Max values

Menus → System → Configure Aux →Aux 1-2

→Min

→Max

Min and Max values are user defined. The range is -10000 to 10000. Min and Max

values are used for scaling the input value received from an analog aux input. The

min and max values may be configured to correspond to the minimum input level

(i.e. 0VDC or 4mA) and maximum input level (i.e. 1VDC, 5VDC, or 20mA). The

Min value must be less than Max value.

Example - when using a total dissolved gas pressure sensor (0-5VDC input type)

enter -400 for min value. The 5400 will display “-400” when the input value is 0VDC.

Set the max value to correspond to the maximum input value as +400. The 5200A

will display “400” when input value is 5VDC.

Notes:

The 5200A will monitor and data log based on the “min” and “max”

-

volt-

age or current signal.

To enter negative values, type the whole number then select “-” on the

-

numeric keypad.

Configuring the 5200A

Whenever min and/or max values are changed, go to

-

Menus → System

→ Sensor Setup → Aux 1-6 → Control Low and Control High menu to

verify control/alarm values are correct for the application.

Display Format

Menus → System → Configure Aux →Aux 1-2→Display Format

Configure the Display format (0, 0.0, or 0.00) based on the resolution to be displayed

on the Run Screen.

Example - when using a total dissolved gas pressure sensor configure, the display

format as 0.0 - figure 4.6, on this page.

In the below screen shot, the Run Screen is displaying aux name “TGP,” suffix

“mmHg,” with display format “0.0”. The display value represents an input of 1.875

volts with 0-5VDC analog aux configuration. The min value = “-400”. The max

value = “+400”. The control/alarm low value is “-50”. Alarms are enabled for this

aux input.

figure 4.6

Notes:

Values are displayed based on the display format resolution. Example - if

-

the display format is 0.0 and the min value configured is 1.88, then 1.9

will be the value displayed in the min value menu.

5200A aux sensor logs record 0.00 resolution regardless of the selected

-

resolution in the aux analog display format configuration.

Wire aux analog devices -

1.

page 49.

Enter Aux menu

2.

Menus → System → Configure Aux →Aux 1-2

Use

3.

and

to scroll and highlight submenus.

Press

4.

to select.

Press

5.

to save configuration.

Configuring the 5200A

Advertising