7. Operation <Practical Steps>

7.6 Operation at Different Acceleration and Deceleration Settings

Example of use in operation) Positioning is performed to the position 150 mm from the home (position 1) at a

speed of 200 mm/sec.
The acceleration is 0.3 G and the deceleration is 0.1 G.

Method)

Set 0.3 [G] in the “Acceleration” field and 0.1 [G] in the “Deceleration” field of the
position table.

Controller

[5] [2]

[1]

[7]

[6] [3]

[8] [4]

[1]

[2]

[3]

[4]

[5]

[6]

[7]

[8]

P

L

C

PIO

Signal name

Start

Command position 1

Command position 2

Command position 4

Command position 8

Command position 16

Command position 32

Completed position 1

Completed position 2

Completed position 4

Completed position 8

Completed position 16

Completed position 32

Position complete

Moving

Category

Input

Output

Reference flow

Select/enter command position 1.

Start input ON

Completed position OFF

Position complete output OFF

Moving output ON

Start input OFF

Moving output OFF

Movement to position 1 completes.

Position complete output turns
ON 0.1 mm before position 1.

Completed position 1 is output.

Movement to position 1 starts at the
maximum acceleration.

Moves at constant speed (200 mm/sec).

Decelerates at 0.1 G.