I/o signal control and signal functions – IAI America ACON-CG User Manual

Page 60

Advertising
background image

46

5. I/O Signal Control and Signal Functions

Controller

Controller

External power supply

Each input

External power supply

Each input

Internal circuit

Internal circuit

5. I/O Signal Control and Signal Functions

5.1 Interface

Circuit

The standard interface specification of the controller is NPN, but the PNP specification is also available as an
option.
To prevent confusion during wiring, the NPN and PNP specifications use the same power line configuration.
Accordingly, there is no need to reverse the power signal assignments for a PNP controller.

5.1.1

External Input Specifications

Item Specification

Number of input points

16 points

Input voltage

24 VDC

r 10%

Input current

5 mA/point

ON voltage: Min. 18 V (3.5 mA)

Operating voltage

OFF voltage: Max. 6 V (1 mA)

Leak current

1 mA or less/point

Isolation method

Photocoupler

Internal circuit configuration

[NPN specification]

[PNP specification]