Code Message

name

Description

30C No connected axis

This message indicates that no controller address is recognized.
Cause: [1] The controller is not operating properly.

[2] Only the supplied communication cable (SGA/SGB) is

disconnected.

[3] If a SIO converter is used, 24V is supplied to the

converter but the link cable is not connected.

[4] The ADRS switch settings are duplicated by mistake

when multiple controllers are linked.

Action: [1] Check if the RDY lamp on the controller is lit. If the lamp

is not lit, the controller is faulty.

[2] If a spare teaching pendant is available, replace the

current pendant with the spare unit, or with a PC, and see
if the message disappears.

[3] Supply power after connecting the link cable between the

converter and controller.

[4] Make sure the ADRS switch settings are not duplicated.

If the message is still displayed after taking the above actions, please
contact IAI.