2) wiring the emergency-stop switch – IAI America ACON-CG User Manual

Page 40

Advertising
background image

26

4. W

iring

(2) Wiring the emergency-stop switch

In many cases multiple controllers are used in a single system.
To provide an emergency-stop function for the entire system, the controller circuit is designed in such a
way that a single EMG switch is able to actuate an emergency stop in all connected controllers.

[Example of recommended circuit]

(Note 1) To cut off the motor drive power supply in conformance with safety category 2, connect 24V to

the EMG terminal and a contactor or other contact device to the MPI/MPO terminals.

(Note 2) The current consumption of the internal relay is 10 mA or less.

Motor
power
supply

External EMG
reset switch

External EMG circuit

EMG switch on

teaching pendant

Relay

ACON-C controller

Coil current:

0.1 A or less

Connection detection circuit

Controller
power
supply

Advertising