60

5. I/O Signal Control and Signal Functions

„ Movement to each position (ST0 to ST2) [Solenoid valve mode 2 (3-point type)]

Since the number of positioning points is limited to three, the actuator can be controlled just like an air cylinder.
While this signal is ON, the actuator will move toward the target position.
If the signal turns OFF while the actuator is moving, the actuator will decelerate to a stop.
Before executing this command, enter a target position in the “Position” field for position No. 0, 1 or 2 in the
position table.

Input signal

Target position

Remarks

ST0

Rear end

The target position is defined in the “Position” field for position No. 0.

ST1

Front end

The target position is defined in the “Position” field for position No. 1.

ST2

Intermediate point The target position is defined in the “Position” field for position No. 2.