IAI America ACON-CG User Manual

Page 162

Advertising
background image

148

10. T

roubleshooting

10.2 Alarm Level Classification

Alarms are classified into two levels based on the corresponding symptoms.

Alarm level

ALM lamp

*ALM signal

What happens when alarm

generates

How to reset

Operation
cancellation

Lit

Output

The actuator decelerates

to a stop and then the

servo turns OFF.

Input an alarm reset signal
(RES) from the PLC.
Reset by the PC/teaching
pendant.

Cold start

Lit

Output

The actuator decelerates

to a stop and then the

servo turns OFF.

Reconnect the power.

(Note) The *ALM output signal is a contact-b signal.

After the power is turned on, this signal will remain ON while the controller is normal, and turn OFF if
an alarm occurs.
Although the *ALM signal will turn OFF when the power is cut off, it cannot be used as a contact-b
interlock.

„ How to reset operation-cancellation level alarms

Input an alarm reset signal (RES) continuously for 6 msec or more.
This resets the *ALM signal to ON, so turn OFF the RES signal after confirming that the *ALM signal is ON.

Caution: Reset each alarm after identifying and removing the cause of the alarm. If the cause of

the alarm cannot be removed or the alarm still persists after the cause has been removed,
contact IAI.
If the same error occurs again after resetting the alarm, it means that the cause of the
alarm still remains.

Alarm reset input signal (RES)

Alarm output signal (*ALM)

Alarm present

6 msec or more

No alarm