IAI America ACON-CG User Manual

Page 39

Advertising
background image

25

4. W

iring

4.1.2

Wiring the Power Supply/Emergency-Stop Switch

(1)

Wiring the power supply

To connect multiple controllers, provide a relay terminal block.
Use a power cable satisfying the following specifications:

Item Specification

Applicable wire length

Single wire:

‡1.0 / Stranded: 0.8 mm

2

, AWG size 18, (copper wire)

Stripped wire length

10 mm

Temperature rating of
isolated sheath

60

qC or above

* Use a flathead screwdriver with a blade end of approx. 2.6 mm to push in the wire.
(Note) Turn on/off the control power on the primary side of the 24-VDC constant power supply.

S1
S2
MPI
MPO
24V
0V
EMG-

24V

OV
FG

Input power supply
24 VDC