IAI America PCON-CFA User Manual

Page 200

Advertising
background image

5. SCON-CA

CC-Link

194

(* “ON” in the table shows the corresponding bit of “1” and “OFF” shows “0”.)

Signal Type

Bit Signal Name

Description

Details

b15

EMGS

Emergency Stop: “ON” for Emergency Stop Status

5.7.11 (2)

b14

PWR

Controller Ready: “ON” for Ready

5.7.11 (1)

b13

ZONE2 Zone 2: “ON” with the current position within the zone set range 5.7.11 (12)

b12

ZONE1 Zone 1: “ON” with the current position within the zone set range 5.7.11 (12)

b11

PZONE

Position Zone:
“ON” with the current position within the position zone set range

5.7.11 (12)

b10

LOAD

Load Output :
“ON” when reached and “OFF” when incomplete
(Refer to instruction manual for the controller main body for
more information)

5.7.11 (26)

b9

TRQS

Torque Level :
“ON” when reached and “OFF” when incomplete
(Refer to instruction manual for the controller main body for
more information)

5.7.11 (27)

b8

RMDS

Operation Mode Status:
“OFF” for currently “AUTO” mode, “ON” for currently
“MANU” mode

5.7.11 (19)

b7

GHMS

Under Homing Operation :
This signal remains ON while home return is in progress.

5.7.11 (6)

b6

PUSHS

Push Motion in Progress :
This signal remains ON while push motion is in progress.

5.7.11 (25)

b5

PSFL

Pressing and a Miss: “ON” for pressing and a miss

5.7.11 (23)

b4

SV

Operation Ready: “ON” with Servo ON

5.7.11 (5)

b3

ALM

Alarm: “ON” with alarm issue

5.7.11 (3)

b2

MOVE

Under Movement Signal:
“ON” during Actuator Movement

5.7.11 (9)

b1

HEND

Homing Completion
“ON” with Homing Completion

5.7.11 (6)

P

LC

In

pu

t

Status

Signal 2

b0

PEND

Positioning Completion Signal:
“ON” with Positioning Completion

5.7.11 (10)