(16) Teaching Mode Command (MODE)

Teaching Mode Signal

(MODES)

When the MODE signal is turned “ON”, the normal operation mode is changed to the teaching mode.
When the mode for the controllers for each actuator is changed to the teaching mode, the MODES
signal is turned ON.
After confirming that the MODES signal is turned “ON” on the PLC side, start the teaching operation.

Note: In order to change the normal operation mode to the teaching mode, the following conditions are required.

x

The actuator operation (motor) is stopped.

x

The + JOG (JOG+) signal and – JOG (JOG-) signal are turned “OFF”.

x

The Position Data Import Command (PWRT) Signal and Positioning Start (CSTR) Signal are turned

“OFF”.

Note: When the PWRT signal is not turned OFF, the mode is not returned to the normal operation mode.

(17) Position Data Import Command (PWRT) Signal

Position Data Import Completion (WEND) Signal

The PWRT signal is available when the teaching mode signal (MODES) is turned “ON”.
Turn ON the PWRT signal (*1). Then, the current position data will be written in the position data box for
the position No. set using the PLC's specified Position No. register (*2).
When the data writing is completed, the WEND signal is turned “ON”.
After the WEND signal is turned ON, turn OFF the PWRT signal in the host machine.
When the PWRT signal is turned ON before the WEND signal is turned “ON”, the WEND signal is not
turned “ON”.
When the PWRT signal is turned “OFF” the WEND signal is also turned “OFF”.

(*1) Turn it ON for 20msec or more. If the time is shorter than 20msec, the writing is not completed.
(*2) When the data items except for the position have not been defined, the parameter initial values are

written (Refer to the instruction manual for the controller main body).

(18) Brake Forcible Release (BKRL) Signal

Turning this signal “ON” can release the brake forcibly.

PLC Output Signal

PLC Input Signal

PLC Output Signal

PLC Input Signal

PLC Output Signal

(PLC→ACON, PCON)

(ACON, PCON→PLC)

(ACON, PCON→PLC)

MODES

PWRT

WEND

20msec or more