5. SCON-CA

CC-Link

237

*1 If CLBR is turn OFF in this period, the calibration process cannot be performed since it is before

input identification.

*2 An alarm will be generated if CLBR is turned OFF in this period

(33) Servo Gain Parameter Set Selection (GSL0, GSL1)

An operation with preset parameters at each position becomes available if 4 sets of servo gain
parameters (6 sets) are registered in advance
Refer to the instruction manual for the controller for more information.

GSL1

GSL0

Function

Reference

OFF

OFF Parameter set 0 selected

Set in delvery

OFF

ON

Parameter set 1 selected

ON

OFF Parameter set 2 selected

ON

ON

Parameter set 3 selected

PLC Output Signal

CLBR

CEND

Input Identification

Continuously for 20ms

*1

Calibration Time

*2

Turn CLBR OFF after confirming CEND is ON.

CEND turns ON after calibration process is completed properly.

If CLBR is OFF, CEND becomes always OFF.

Advertising