Acon-c/cg, pcon-c/cg cc-link – IAI America PCON-CFA User Manual

Page 52

Advertising
background image

3.

ACON-C/CG, PCON-C/CG

CC-Link

46

(* “ON” in the table shows the corresponding bit of “1” and “OFF” shows “0”.)

Signal Type

Bit

Signal name

Description

Details

Current

Position

32bits

Data



32-bit Signed Integer
The unit is 0.01mm.
(Example)
Read Value: 000003FF

H

= 1023 (decimal system) = 10.23mm

* When the value is read in hexadecimal notation, the negative figure

is expressed as a compliment of 2.

3.9 (3)

Command

Current

32bits

Data



32-bit Integer
It shows the current value in the current command.
The unit is mA.
Read Value: 000003FF

H

= 1023 (decimal system) = 1023mA

3.9 (3)

Current

Speed

32bits

Data



32-bit Signed Integer
It shows the current speed.
Positive Figure: Under movement in the opposite direction of the
home
Negative Figure: Under movement in the home direction
The unit is 0.01mm/sec.
(Example)
Read Value: 000003FF

H

= 1023 (decimal system) = 10.23mm/sec

* When it is read in hexadecimal notation, input the negative value

using a compliment of 2.

3.9 (3)

Alarm

code

16bits

Data



16-bit Integer
When an alarm is issued, the alarm code is output.
When any alarm is not issued, it is “0”.
Refer to the instruction manual for the controller main body for the
details of the alarms.

3.9 (3)

b15

EMGS

Emergency Stop: “ON” for Emergency Stop Status

3.7.7 (2)

b14

PWR

Controller Ready: “ON” for Ready

3.7.7 (1)

b13

ZONE2

Zone 2: “ON” for the current position within the zone set range

3.7.7 (12)

b12

ZONE1

Zone 1: “ON” for the current position within the zone set range

3.7.7 (12)

b11

ZONE

Position Zone:
“ON” when the current position is within the position zone set range

3.7.7 (12)

ACON



Unavailable (ON/OFF is undefined)



b10

PCON LOAD

Load Output Judgment
“ON” for Reached “OFF” for Not reached
(Refer to the instruction manual for the controller main body for more
information).

3.7.7 (26)

ACON



Unavailable (ON/OFF is undefined).



b9

PCON TRQS

Torque Level:
“ON” for Reached “OFF” for Not Reached
(Refer to the instruction manual for the controller main body for more
information).

3.7.7 (27)

b8

RMDS

Operation Mode Status:
“OFF” for currently “AUTO” mode, “ON” for currently “MANU” mode

3.7.7 (19)

b7

GHMS

Under Homing Operation: “ON” for Homing Operation

3.7.7 (6)

b6

PUSHS

Under Pressing Operation: “ON” for Pressing Operation

3.7.7 (25)

b5

PSEL

Pressing and a Miss: “ON” for pressing and a miss

3.7.7 (23)

b4

SV

Operation Ready: “ON” with Servo ON

3.7.7 (5)

b3

ALM

Alarm: “ON” with alarm issue

3.7.7 (3)

b2

MOVE

Movement Signal: “ON” with Actuator Movement

3.7.7 (9)

b1

HEND

Homing Completion: “ON” with Homing Completion

3.7.7 (6)

PLC Input

Status
Signal

b0

PEND

Positioning Completion Signal: “ON” with Positioning Completion

3.7.7 (10)