Alarm Output Relay Operation

The FX can generate a contact signal from an alarm output relay (/A[ ] and /A4A options)
when an alarm occurs. The alarm output relay operation can be changed.
For the setting procedure, see section 3.5.

Alarm

Alarm output relay

(Reflash on)

Alarm output relay

(Reflash off)

Channel 1

Channel 3

Channel 2

Energize or De-energize

AND/OR

Alarm

Channel 1

AND

Channel 2

OR

Alarm output relay

or

internal switch

NO

Energize

De-energize

C NC

NO C NC

NO C NC

NO C NC

NO C NC

NO C NC

When power

is shut down

NO: Normally Opened

C: Common

NC: Normally Closed

Normal

operation

When an alarm

is occurring

Alarm

Normal

Alarm

Normal

Reflash

(You can set AND/OR for the alarm output relay and internal

switch. For details about the internal switch, see the next

page.)

(when a relay is set to OR logic)

Normal

Reset

Relay

Action on

ACK

Relay

Action on

ACK

Occurrence

Activated

Deactivated

Activated

Deactivated

Activated

Deactivated

Release

or

Activated

Deactivated

or

Display

Alarm

Hold

Non-hold

Alarm output relay

Hold

Non-hold

Hold

Non-hold

Non-hold/Hold

Relay is activated

at the next scan

interval.

Relay is activated

when the next

alarm occurs.

Alarm ACK

Alarm ACK

500 ms

• Reflash

When multiple alarms are assigned to one alarm output relay, this function notifies the

occurrence of subsequent alarms after the relay is activated by the first alarm. When
subsequent alarms occur, the output relay is released temporarily. The relays are
deactivated for 500 ms.

The reflash function is set on the first three output relays

*

.

* I01 to I03. I01 and I02 for the /A1 option.

Note

When reflash is enabled, the first three output relays are used exclusively as reflash relays. The
first three output relays are set to OR logic and non-hold operation regardless of the AND/OR
and non-hold/hold settings explained below.

• AND/OR

When multiple alarms are assigned to one alarm output relay, the condition for

activating the output relay can be selected from the following: You can select AND
operation also for the internal switch.
• AND: Activated when all assigned alarms are occurring simultaneously.
• OR: Activated when any of the specified alarms is occurring.

1.2 Alarms