Setup screen – Yokogawa Value Series FX1000 User Manual

Page 95

Advertising
background image

3-22

IM 04L21B01-01EN

Measurement Element

Unit

Expression

Active or regenerative energy

Wh

TLOG.SUM(_WAT_)

Active energy

Wh

TLOG.SUM(_WATP_)

Regenerative energy

–Wh

TLOG.SUM(_WATN_)

Reactive energy (LAG: +)

Varh

TLOG.SUM(_VARP_)

Reactive energy (LEAD: –)

–Varh

TLOG.SUM(_VARN_)

Apparent energy

Vah

TLOG.SUM(_VA_)

• Report Function

By using the report function, you can output electric energy as a power measurement

channel’s hourly, daily, or monthly report. In addition, on the stacked bar graph display,
you can also display a list of items such as the total electric energy for a month and
the electric energy for each day of the month (see example 5 in this section).

Update Interval of Measurement Elements

The update interval for each of the power measurement elements is 1 second.

Setup Screen

• Setting the Phase, Wiring System, and Input Voltage

Press

MENU (to switch to setting mode), hold down FUNC for 3 s (to switch to basic

setting mode), and select the

Menu tab > Power

• Setting the VT Ratio, CT Ratio, and Low-Cut Power

Press

MENU (to switch to setting mode), and select the Menu tab > Power.

• Setting the Power Computation

Press

MENU (to switch to setting mode), and select the Menu tab > Math channel >

Expression, Alarm

3.12 Measuring Power (/PWR1 Option)

Advertising