10 counting pulses (/pm1 option), 10 counting pulses (/pm1 option) -17 – Yokogawa Value Series FX1000 User Manual

Page 90

Advertising
background image

Measurement Channels and

Alarms

IM 04L21B01-01EN

3-17

3

2

1

4

5

6

7

8

9

10

11

12

13

14

App

Index

3.10 Counting Pulses (/PM1 Option)

The pulses applied to the pulse input terminal are counted on a computation channel.
For a description of the function, see section 1.1.

Setup Screen

Press

MENU (to switch to setting mode), and select the Menu tab > Math channel >

Expression, Alarm

Setup Items

• First-CH, Last-CH

Select the target computation channels.

• Math

Select

On.

• Math > Calculation expression

Enter the equation using symbols.
Q01 to Q08: Displays the number of pulses per second.
P01 to P08: Displays the number of pulses per scan interval.

* The numbers 01 to 08 correspond to the pulse input terminal numbers.

For the procedure to set the computation channels, see section 9.1.

The procedure is explained below using examples.

• Example 1: Pulse Sum Value

Display the sum value of the pulse signal applied to pulse input terminal number 6.

Number of pulses

per scan interval

TLOG.SUM

Pulse sum value

Pulse input

Scan interval

Time

(Sum)

P6

Expression

The following table shows which calculation expression to assign to which computation

channel. Set the span lower/upper limit and unit according to the application.

Channel

Expression

Description

101

TLOG.SUM(P6)

Sum of the number of pulses per scan interval

Advertising