Code

Message

285

FTP data connection error.

Further details are provided by the character string that appears after error code 285.
Character String and Details

SOCKET

Failed to create a socket for the transfer connection.

2

BIND

Failed the transfer connection command.

2

CONNECT

Failed the transfer connection.

2

LISTEN

Failed the transfer connection reception.

2

ACCEPT

Failed to accept the transfer connection.

2

SOCKNAME

Internal processing error.

1

RECV

Failed to receive data over the transfer connection.

2

SEND

Failed to send data over the transfer connection.

2

286

FTP file transfer error.

290

SNTP access failure.

Further details are provided by the character string that appears after error code 290.
Character String and Details

DORMANT

Internal processing error.

1

LINK

Data link is disconnected.
Check the cable connection.

291

SNTP server does not respond.

Further details are provided by the character string that appears after error code 291.
Character String and Details

TIMEOUT

Check that the server is running.

2

292

Incorrect SNTP server setting.

Further details are provided by the character string that appears after error code 292.
Character String and Details

HOSTNAME

Failed the DNS lookup (search the IP address corresponding to the host name).
Check the DNS setting and the SNTP server name.

TCPIP

Internal processing error.

1

293

Invalid SNTP server reply.

Further details are provided by the character string that appears after error code 293.
Character String and Details

SEND

A correct IP address has not been assigned to the FX.
Check the IP address.

BROKEN

There is a problem with the SNTP server.
If this error occurs even after executing SNTP manually several times, check the SNTP server.