2 setup examples of event action, 2 setup examples of event action -5 – Yokogawa Value Series FX1000 User Manual

Page 194

Advertising
background image

7-5

IM 04L21B01-01EN

Customizing

Actions Using the Event

Action and

Remote Control Functions (/R1 and /PM1 Options)

3

2

1

4

5

6

7

8

9

10

11

12

13

14

App

Index

7.2 Setup Examples of Event Action

Example 1: Starting/Stopping the Memory Sampling through Remote Control

(/R1 Option)

Starts/Stops the memory sampling when a signal is applied to remote control input
terminal 2. Use logic box number 1.

• Setup Screen and Setup Items

Press

MENU (to switch to setting mode), and select the Menu tab > Timer, Event

action > Event action.

<Operation>

If the input to the remote control input terminal 2 is turned ON when memory sampling
is stopped, memory sampling starts. If the remote control input is turned OFF when
memory sampling is in progress, memory sampling stops.

Example 2: Writing a Message When an Alarm Occurs

Write the message “Channel 1 Alarm” to group 1 when an alarm occurs on channel 1.
Use logic box number 2.

• Setup Screen and Setup Items

Press

MENU (to switch to setting mode), and select the Menu tab > Timer, Event

action > Event action.

<Other Settings>

• Set an alarm to channel 1 and output to internal switch 3.
• Register “Channel 1 alarm” in message number 4.
For the procedure to set the alarm, see section 3.7.
For the procedure to set the message, see section 5.4.