Alarms – Yokogawa Value Series FX1000 User Manual

Page 267

Advertising
background image

13-2

IM 04L21B01-01EN

Item

Specifications

Thermocouple burnout

Burnout upscale/downscale selectable (for each channel).
Normal: 2 kΩ or less, Burnout: 100 kΩ or more (parallel capacitance of 0.01 µF or less)
Detection current: Approx. 10 µA

1-5 range burnout

Burnout upscale/downscale selectable (for each channel).
Burnout detection: Greater than “scale upper limit + 10% of scale width” (upscale), or

“scale lower limit – less than 5% of scale width” (downscale)

TC reference junction compensation

Internal reference junction compensation or external reference junction compensation

Filter function

Takes the moving average of the input values (for each channel).

Moving average data points: 2 to 400

Computation

Difference computation

Computable range:

DC voltage, TC, RTD, and DI

Linear scaling

Computable range:

DC voltage, TC, RTD, and DI

Scalable range:

–30000 to 30000. The decimal place is within 4 digits to the right

of the decimal point.

Unit:

Up to 6 characters in length

Over value detection:

The value can be set to over value when ±5% of the scale range

is exceeded.

Square root computation Takes the square root of the input and apply linear scaling

Computable type:

DC voltage

Scalable range and unit:

Same as linear scaling

Low-cut:

Set the low-cut value in the range of 0.0% to 5.0% of the span.

Over value detection:

Same as linear scaling

1-5V

Computable range:

1 to 5 V

Scalable range and unit:

Same as linear scaling

Low-cut:

The low-cut point is fixed to the span lower limit.

Over value detection:

Same as linear scaling

Alarms

Item

Specifications

Number of alarms

Up to 4 alarms (levels) per measurement channel

Alarm type

High limit, low limit, difference high limit, difference low limit, high limit on rate-of-change alarm, low

limit on rate-of-change alarm, delay high limit, and delay low limit

Alarm delay time

1 to 3600 s (for each channel)

Rate-of-change calculation interval of rate-of-change alarms

1 to 32 times the scan interval (common to all channels)

Alarm output

Output to the internal switch

Number of internal switches: 30

Internal switch operation: AND/OR operation selectable

Hysteresis

High and low limit alarm:

0.0 to 5.0% of the span (common to all channels)

Difference high and low limit alarms: 0.0 to 5.0% of the span (common to all channels)

Display

Displays the status on the respective operation screen and an alarm icon on the status display

section when an alarm occurs.

Display operation: Hold or not hold the display until the alarm acknowledge operation.

Alarm hide function (alarm no logging function)

Not display alarms nor record to the alarm summary (for each channel)

Alarm information

Displays a log of alarm occurrences on the alarm summary.

13.1 Signal Input and Alarms