4 other standard functions, 4 other standard functions -8, Event action function – Yokogawa Value Series FX1000 User Manual

Page 273: Security function, Time related functions, Types of characters that can be handled, Miscellaneous

Advertising
background image

13-8

IM 04L21B01-01EN

13.4 Other Standard Functions

Event Action Function

Item

Specifications

Event action

Execute a specified operation when a given event occurs.

Number of settings

40

Events

Remote control input, etc.

Timer

Number of timers: 4

Match time timer

Number of timers: 4

Action

Specify memory start/stop, alarm ACK, etc.

There are limitations on the combinations of events and actions.

Security Function

Item

Specifications

Key lock function

Limitations to key operation, access to the external storage medium (on FXs with a CF card slot or

the /USB1 option), and various operations

Login function

Only registered users can operate the FX.

System administrators

5 administrators (with total operation access)

Users

30 users (with access to operations based on their user access rights)

User access rights setting Limitations to key operation, access to the external storage medium (on FXs with a CF card slot or

the /USB1 option), and various operations

Automatic logout function Users are logged out automatically if there are no key operations for the specified period of time.

Time Related Functions

Item

Specifications

Clock

With a calendar function

Accuracy

±50 ppm (0 to 50°C); does not include the delay (1 second or less) that occurs when the power is

turned on

Time setting

Set by way of key operations, communication commands (/C2, /C3, and /C7), the event action

function, or the SNTP client function (/C7)

Time adjustment method
While memory sampling Corrects the time by 40 ms for each second.

Limit in which the time is gradually adjusted: Select from the available settings between 10 s and 5

min.

If the time is outside the limit, the time is immediately corrected.

Cannot be used after hour 0 on January 1st, 2038.

While memory is stopped Immediately change the time.
DST

The date/time for switching between standard time and DST can be specified.

Time zone

Sets the time difference from GMT.

Date format

Select YYYY/MM/DD, MM/DD/YYYY, DD/MM/YYYY, or DD.MM.YYYY.

Types of Characters That Can Be Handled

Item

Specifications

Characters

Alphabet characters, numbers, and symbols (limitation exists)

Miscellaneous

Item

Specifications

Decimal point type

Period or comma

Advertising