An example of the relay action when alarm ACK is executed is shown below. This

example is for the case when the output relay

AND item is set to None.

Normal

Alarm ACK

Alarm output relay

Alarm 2

Alarm 1

Relay is activated in the next scan interval

Activated

Alarm

occurrence

Alarm

occurrence

Deactivated

Reset

Alarm ACK

Relay is activated on the next alarm occurrence

Alarm output relay

Alarm 2

Alarm 1

Activated

Alarm

occurrence

Alarm

occurrence

Deactivated

• Hysteresis > Meas CH

• High/Low

Sets the hysteresis width of the alarm occurrence/release of the high/low limit alarm

specified on measurement channels.

Selectable range: 0.0% to 5.0% of the span or scaling width
If you set a limit to a channel that is set to log scale (/LG1 option), the alarm

hysteresis will be fixed to 0%.

• Delta High/Low

Sets the hysteresis width of the alarm occurrence/release of the difference high/low

limit alarm specified on measurement channels.

Selectable range: 0.0% to 5.0% of the span

• Hysteresis > Math CH (/M1, /PM1, and /PWR1 options)

Sets the hysteresis width of the alarm occurrence/release of the high/low limit alarm

specified on computation channels.
Selectable range: 0.0% to 5.0% of the measurement span

3.5 Setting the Auxiliary Alarm Function