POINT I/O Module Data 107

60 Hz - 100 ms update rate

250 Hz - 24 ms update rate

500 Hz - 12 ms update rate

The update rate determines the rate at which the inputs are sampled. Maximum
update rate is determined by the notch filter setting. The notch filter parameter is
used to select the fastest possible rate. Minimum update rate is 10,000 ms.

Alarms

Available alarms include the following:

Low

Low Low

High

High High

Each alarm has one status bit which is set to indicate when the input goes beyond
its set point. All Alarm Status bits can be read individually or from the Channel
Status Byte (bits 2…5).

You can configure each channel alarm individually.

Range Status

The module reports both Under Range and Over Range status.

Under Range Status - This bit (Channel Status Bit 6) is set when the
module returned data is at a minimum.

For the 1734-IE2C module, the value is 98 counts
(around 120

μ

A).

For the 1734-IE2V module, the value is -0.25 or -10.25V, depending on
mode.

When set, the channel status indicator blinks red.

On the 1734-IE2C module, a wire-off condition sets this bit.

Over Range Status - This bit (Channel Status Bit 7) is set when the
module returned data is at a maximum.

For the 1734-IE2C module, the value is around 21 mA

For the 1734-IE2V module, the value is +10.25V.

When set, the channel status indicator blinks red.

On the 1734-IE2V module, a wire-off condition sets this bit.