Rockwell Automation 1734-XXXX POINT I/O Digital and Analog Modules and POINTBlock I/O Modules User Manual

Page 140

Advertising
background image

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013

142 Troubleshoot with the Indicators

1734-OB2E, 1734-OB4E, and 1734-OB8E Source Output Modules

1734-OB2, 1734-OB4, and 1734-OB8 Source Output Modules

1734-OB2E

1734-OB4E

24VDC

Source
Output

Module

Status

Network

Status

1734
OB4E

NODE:

0

1

2

3

24VDC

Source
Output

Module

Status

Network

Status

1734
OB2E

NODE:

0

1

1734-OB8E

24VDC

Source
Output

Module

Status

Network

Status

1734
OB8E

0

1

2

3

NODE:

4

5

6

7

Module Status

Network Status

Module Status

Network Status

Module Status

Network Status

Status of Output 0

Status of Output 1

Status of Output 0

Status of Output 1

Status of Output 2

Status of Output 3

Status of Output 0 & 4

Status of Output 1 & 5

Status of Output 2 & 6

Status of Output 3 & 7

Indication

Probable Cause

Recommended Action

I/O Status

Off

All outputs are inactive.

None.

Yellow

One or more output is active and under control.

None.

Flashing red

Open circuit detected - no load (Off-state only).

Connect load or disable no load detection.

Solid red

Short circuit detected (On-state only).

Remove short or overloaded circuit.

Module Status

Network Status

Status of Output 0

Status of Output 1

Status of Output 2

Status of Output 3

1734-OB2

1734-OB4

Status of Output 0 & 4

Status of Output 1 & 5

Status of Output 2 & 6

Status of Output 3 & 7

Module Status

Network Status

1734-OB8

24VDC

Source
Output

Module

Status

Network

Status

1734

OB2

0

1

NODE:

24VDC

Source
Output

Module

Status

Network

Status

1734

OB4

0

1

2

3

NODE:

24VDC

Source
Output

Module

Status

Network

Status

1734

OB8

0

1

2

3

NODE:

4

5

6

7

Status of Output 0

Status of Output 1

Module Status

Network Status

Indication

Probable Cause

Recommended Action

I/O Status

Off

All outputs are inactive.

None.

Yellow

One or more outputs is active and under control.

None.