Troubleshoot analog modules, 1734-ie2c analog current input module, 1734-oe2c analog current output module – Rockwell Automation 1734-XXXX POINT I/O Digital and Analog Modules and POINTBlock I/O Modules User Manual

Page 145

Advertising
background image

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013

Troubleshoot with the Indicators 147

Troubleshoot Analog
Modules

Each analog module has I/O indicators to show the status of the inputs/outputs.
Refer to the individual module for I/O status information.

1734-IE2C Analog Current Input Module

1734-OE2C Analog Current Output Module

41974

Module Status

Network Status

Status of Input 0

Status of Input 1

4-20mA

Analog

Input

Module

Status

Network

Status

1734

IE2C

NODE:

0

1

Indication

Probable Cause

Recommended Action

Channel Status

Off

Module is in CAL mode.

None.

Solid green

Normal operation present with channel scanning inputs.

None.

Flashing green

Channel being calibrated.

None.

Solid red

No power or major channel fault present.

Apply field power, or replace module, as needed.

Flashing red

Channel is at end of range (0 mA or 21 mA).

Operate within normal range.

41974

Module Status

4-20mA

Analog
Output

Module

Status

Network

Status

1734
OE2C

NODE:

0

1

Network Status

Status of Output 0

Status of Output 1

Indication

Probable Cause

Recommended Action

Channel Status

Off

Module is in CAL mode.

None.

Solid green

Channel actively controlling outputs

None.

Flashing green

Channel calibrating.

None.

Solid red

Unrecoverable fault may require device replacement.

Replace device.

Flashing red

No power, or open wire present.

Apply power or verify wiring to load, and correct, as needed.