Work with dialogs for digital output modules, Enter values on the fault/program action dialog, Working with dialogs for digital output modules – Rockwell Automation 1734-XXXX POINT I/O Digital and Analog Modules and POINTBlock I/O Modules User Manual

Page 178

Advertising
background image

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013

186 Configure POINT I/O Modules in RSLogix 5000 Software

3. From the Configuration dialog, complete entries for Input Filter Time

(ms) for Off-On and On-Off for each point, referring to the table.

4. From the Configuration dialog, perform one of the following:

Click another tab at the top of the dialog.
or

Click OK to save changes and close the dialog.
or

Click Cancel to return to default values.
or

Click Apply to save changes you made on any of the dialogs and
continue to display the dialog, noting that you enable the Apply button
when you make changes to any of the dialogs.

Work with Dialogs for Digital Output Modules

Read this section to complete the Fault/Program Action and Configuration
dialogs for output modules. You typically select these dialogs from the General
dialog, when you add an output module with the following entries for
connection type:

Data

Rack Optimization

Enter values for the Fault/Program Action and Configuration dialogs based on
the following output modules:

Without diagnostic status

With overload diagnostic status

With overload and open load diagnostic status

Enter Values on the Fault/Program Action Dialog

Enter values on this dialog to configure the module output state for output
modules when the controller mode changes to Program or Fault mode. To make
these entries, follow these procedures.

Feature

Description

Channel

Displays channels you use to set channel configuration parameters

Input Filter
Time

Displays Off to On or On to Off transition filter constant

A high signal must be present for this amount of time before the module

reports an On.

a low signal must be present for this amount of time before the module

reports an Off.

Enter a value in milliseconds.

The default is 1 ms (1000 ms).

Advertising