128 Calibrate Your Analog Modules

10. Enter the value shown on your DVM for the Channel Low Value (4.044 in

the example).

11. From the Device Parameters dialog, select the Output High Value, and

download to the module.

12. From the Device Parameters dialog, enter the value shown on the DVM,

which is 20.231 in this example.

13. Repeat these steps for the other channel.
14. From the Device Parameters dialog, click All and Finish Calibration to

complete the calibration process.