Digital ac input modules – Rockwell Automation 1734-XXXX POINT I/O Digital and Analog Modules and POINTBlock I/O Modules User Manual

Page 95

Advertising
background image

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013

POINT I/O Module Data 97

Digital AC Input Modules

T

he 1734 digital AC input modules feature the following:

120 or 220V AC nominal are AC inputs

Input range of 65…132 for 120V AC inputs; 159…264 for 220V AC
inputs

Two sinking style inputs

Autobaud (will match baud of existing devices on the network)

Selectable input filter times (0…65 ms with 1 ms default)

Sequential auto addressing

I/O messages are sent to (consumed) and received from (produced) these
POINT I/O modules. These messages are mapped into the processor memory.

(1)

Default Data Map for 1734-IB4D Module - - Configuration Assembly Instance 103

Message Size: 18 Bytes

7

6

5

4

3

2

1

0

Consume 0

Input 0 Off to On Filter Byte 0

Consume 1

Input 0 Off to On Filter Byte 1

Consume 2

Input 0 On to Off Filter Byte 0

Consume 3

Input 0 On to Off Filter Byte 1

Consume 4

Input 1 Off to On Filter Byte 0

Consume 5

Input 1 Off to On Filter Byte 1

Consume 6

Input 1 On to Off Filter Byte 0

Consume 7

Input 1 On to Off Filter Byte 1

Consume 8

Input 2 Off to On Filter Byte 0

Consume 9

Input 2 Off to On Filter Byte 1

Consume 10

Input 2 On to Off Filter Byte 0

Consume 11

Input 2 On to Off Filter Byte 1

Consume 12

Input 3 Off to On Filter Byte 0

Consume 13

Input 3 Off to On Filter Byte 1

Consume 14

Input 3 On to Off Filter Byte 0

Consume 15

Input 3 On to Off Filter Byte 1

Consume 16

Autobaud Disable

Enable OW3

Enable OW2

Enable OW1

Enable OW0

Consume 17

Produced Assembly Instance

Produce (Tx)

No produced data

Where: OW = open wire.

(1) These are mapped through scan lists in DeviceNet networks and Direct, Listen Only, or Rack-optimized

connections in ControlNet and EtherNet/IP networks.