Rockwell Automation Publication 1734-UM001E-EN-P - July 2013

Install POINTBlock I/O Modules 79

Output Wiring Diagram

Outputs are electronically protected to 0.75 A. Module outputs are selectable for
latched mode or auto-reset mode. (Latched/auto reset is set by module, not by
individual channel.) Each channel is assigned a bit in the data table to indicate the
faulted condition. Outputs in the latched mode can only be reset with a user
command to the module.

ATTENTION: When connecting more than one wire in a
termination point, make sure that both wires are the same gauge
and type.

Channel

Output Terminal

Common Terminal

Power

Remote Termination Block 3

Channel 0

0

6

Channel 1

1

7

Channel 2

2

4

Channel 3

3

5

Remote Termination Block 4

Channel 4

0

6

Channel 5

1

7

Channel 6

2

4

Channel 7

3

5

Module power is supplied from the internal power bus.

ATTENTION: When connecting more than one wire in a
termination point, make sure that both wires are the same gauge
and type.

Out 0 Out 1

Out 3

Out 2

C

C

C

C

Load

Load

Load

Load

V = 12/24V dc, C = Common
Field power is supplied from internal power bus

0

2

6

3

1

7

4

5