148 Troubleshoot with the Indicators

1734-IE2V Analog Voltage Input Module

1734-OE2V Analog Voltage Output Module

41974

Module Status
Network Status

Status of Input 0

Status of Input 1

Analog

Voltage

Input

Module

Status

Network

Status

1734

IE2V

NODE:

0

1

Indication

Probable Cause

Recommended Action

Channel Status

Off

Module is in CAL mode.

None.

Solid green

Normal operation present with channel scanning inputs.

None.

Flashing green

Channel being calibrated.

None.

Solid red

No power or major channel fault present.

Apply field power, or replace module, as needed.

Flashing red

Channel is at end of range (-0.25, -10.25, or +10.25V).

Operate within normal range.

41974

Module Status
Network Status

Status of Output 0

Status of Output 1

Analog

Voltage

Output

Module

Status

Network

Status

1734
OE2V

NODE:

0

1

Indication

Probable Cause

Recommended Action

Channel Status

Off

Module is in CAL mode.

None.

Solid green

Normal operation present with channel actively controlling outputs.

None.

Flashing green

Channel being calibrated.

None.

Flashing red

A Low or High Clamp alarm is present.

Operate within normal range.

Solid red

No field power is present.

Apply field power.

Advertising