1734-ob2ep protected output module, I/o status, Indication probable cause recommended action – Rockwell Automation 1734-XXXX POINT I/O Digital and Analog Modules and POINTBlock I/O Modules User Manual

Page 141

Advertising
background image

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013

Troubleshoot with the Indicators 143

1734-OB2EP Protected Output Module

1734-IV2, 1734-IV4, and 1734-IV8 Source Input Modules

Protected

Sourcing

Output

Module

Status

Network

Status

1734

OB2EP

NODE:

0

1

41974

Module Status

Network Status

Status of Output 0

Status of Output 1

Indication

Probable Cause

Recommended Action

I/O Status

Off

All outputs are inactive.

None.

Yellow

One or more output is active and under control.

None.

Flashing red

Open circuit detected - no load (Off-state only).

Connect load or disable no load detection.

Solid red

Short circuit detected (On-state only).

Remove short or overloaded circuit.

24VDC

Source

Input

Module

Status

Network

Status

1734

IV2

NODE:

0

1

24VDC

Source

Input

Module

Status

Network

Status

1734

IV4

NODE:

0

1

2

3

41974

Module Status

Network Status

Status of Input 0

Status of Input 1

1734-IV2

1734-IV4

24VDC

Source

Input

Module

Status

Network

Status

1734

IV8

NODE:

0

1

2

3

4

5

6

7

1734-IV8

Module Status

Network Status

Status of Input 0 and 4

Status of Input 1 and 5

Status of Input 2 and 6

Status of Input 3 and 7

Status of Input 0

Status of Input 1

Status of Input 2

Status of Input 3

Module Status

Network Status

Indication

Probable Cause

Recommended Action

I/O Status

Off

Input is in the off-state.

None.

Yellow

Input is in the on-state.

None.