Rockwell Automation 1734-XXXX POINT I/O Digital and Analog Modules and POINTBlock I/O Modules User Manual

Page 185

Advertising
background image

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013

Configure POINT I/O Modules in RSLogix 5000 Software 193

You see a Configuration dialog for a current or voltage module, based on
the type of module you added. See the figure for a Configuration dialog
for a current input module.

2. From the Configuration dialog, complete entries, referring to the table.

3. From the bottom of the Configuration dialog, perform one of the

following:

Click another tab at the top of the dialog.
or

For This Value

Select

Comments

High Engineering

-32768…32767

Default for 1734-IE2C analog input module is 16383.
Default for 1734-IE2V analog input module is 10000.

Low Engineering

-32768…32767

Default for 1734-IE2C analog input module is 3277.
Default for 1734-IE2V analog input module is 0.

Digital Filter (ms)

0…10000

Default is 0.

Current Range

4…0 mA
0…20 mA

Default is 4…20 mA.

Voltage Range

-10…10V
0…10V

Default is 0…10V

Real Time Sample (ms)

0…10000

Default is 100.
Refer to the Real Time Sample Values table for the relationship between
Notch Filter and Real Time Sample.

Notch Filter

50 Hz
60 Hz
250 Hz
500 Hz

Default is 60 Hz.
Refer to the Real Time Sample Values table for the relationship between
Notch Filter and Real Time Sample.

Real Time Sample Values

Real Time
Sample

Notch Filter Setting

50 Hz

60 Hz

250 Hz

500 Hz

Min

120 ms

100 ms

24 ms

12 ms