Rockwell Automation 1734-XXXX POINT I/O Digital and Analog Modules and POINTBlock I/O Modules User Manual

Page 114

Advertising
background image

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013

116 POINT I/O Module Data

The 1734D-IA8XOA8

module produces one byte of input data (scanner Rx)

status. It consumes one byte of output data (scanner Tx).

The 1734D-IA8XOW8 module produces one byte of input data (scanner Rx)
status) It consumes one byte of output data (scanner Tx).

The 1734D-IA16

module produces two bytes of input data (scanner Rx). It does

not consume output data (scanner Tx).

For 1734D-IB16 modules, I/O messages are sent to (consumed) and received
from (produced) the POINTBlock I/O modules. These messages are mapped
into the processor’s memory. This module produces two bytes of input data
(scanner Rx) and does not consume output data (scanner Tx).

Default Data Map for the 1734D-IA8XOA8 AC Input/Output Module

Message Size: 1 Byte

7

6

5

4

3

2

1

0

Produces
(scanner Rx)

Ch7

Ch6

Ch5

Ch4

Ch3

Ch2

Ch1

Ch0

Input Data

Where: 0 = off, 1 = on

Message Size: 1 Byte

7

6

5

4

3

2

1

0

Consumes
(scanner Tx)

Ch7

Ch6

Ch5

Ch4

Ch3

Ch2

Ch1

Ch0

Output Data

Where: 0 = off, 1 = on

Default Data Map for the 1734D-IA8XOW8 AC Input/Relay Output Module

Message Size: 1 Byte

7

6

5

4

3

2

1

0

Produces
(scanner Rx)

Ch7

Ch6

Ch5

Ch4

Ch3

Ch2

Ch1

Ch0

Input Data

Where: 0 = off, 1 = on

Message Size: 1 Byte

7

6

5

4

3

2

1

0

Consumes
(scanner Tx)

Ch7

Ch6

Ch5

Ch4

Ch3

Ch2

Ch1

Ch0

Output Data

Where: 0 = off, 1 = on

Default Data for the 1734D-IA16 Module

Message Size: 2 Bytes

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

Produces (Rx)

I15 I14 I13 I12 I11 I10 I9 I8 I7 I6 I5 I4 I3 I2 I1 I0

Consumes (Tx)

No consumed data

Where: I0 = channel 0, I1 = channel 1; 0 = off, 1 = on

Advertising