98 POINT I/O Module Data

These POINT I/O modules produce one byte of input data (scanner Rx). They
do not consume I/O data (scanner Tx).

Digital Output Modules

Read this section for information about digital output modules.

Digital DC Output Modules

The features of DC output modules include the following:

24V DC outputs with a range of 10…28.8V dc

Output diagnostic features are incorporated to assist in troubleshooting

Current limited outputs of up to 2 A with respect to their DC return

Autobaud (will match baud of existing devices on the network)

Sequential auto addressing

I/O messages are sent to (consumed) and received from (produced) these
POINT I/O modules. These messages are mapped into the processor memory.

(1)

These POINT I/O modules produce one byte of input data (scanner Rx). They
consume one byte of output data (Scanner Tx).

Default Data Map for the 1734-IA2 and 1734-IM2 Input Modules

Message Size: 1 Byte

7

6

5

4

3

2

1

0

Produces (scanner Rx)

Ch1

Ch0

Consumes (scanner Tx)

No consumed data

Where: Ch0 = channel 0, Ch1 = channel 1; 0 = off, 1 = on

Default Data Map for the 1734-IA4 and 1734-IM4 Input Modules

Message Size: 1 Byte

7

6

5

4

3

2

1

0

Produces (scanner Rx)

Ch3

Ch2

Ch1

Ch0

Consumes (scanner Tx)

No consumed data

Where: Ch0 = channel 0, Ch1 = channel 1; Ch2 = channel 2, Ch3 = channel 3,
0 = off, 1 = on