Rockwell Automation Publication 1734-UM001E-EN-P - July 2013

POINT I/O Module Data 101

Relay Output Modules

The relay output modules consist of 1734-OW2 and 1734-OW4 2-relay output
modules and 1734-OX2 4-relay output modules. Features of the 1734-OW2 and
1734-OW4 relay modules include the following:

Type A Normally Open relays

Sink or source a current with respect to power or return

Contact outputs isolated from each other

Each output rated 5…240V dc/V rms at 2 A (current is load dependant)

Autobaud (will match baud of existing devices on the network)

Sequential auto addressing

Features of the 1734-OX2 relay modules include the following:

Two Form C isolated (normally open; normally closed)
electromechanical relays

Sink or source a current with respect to power or return

Contact outputs isolated from each other

Each output rated 5…240V dc/V rms at 2 A (current is load dependant)

Autobaud (will match baud of existing devices on the network)

Sequential auto addressing

I/O messages are sent to (consumed) and received from (produced) these
POINT I/O modules. These messages are mapped into the processor memory.

Default Data Map for 1734-OA4 Modules

7

6

5

4

3

2

1

0

Produces (scanner Rx)

No produced data

Consumes (scanner Tx)

Not used

Ch
3

Ch 2 Ch

1

Ch
0

Channel
state

Where: 0 = Off, 1 = On

Default Data Map for the 1734-OW2 Output Module

Message Size: 1 Byte

7

6

5

4

3

2

1

0

Produces
(scanner Rx)

No produced data

Consumes
(scanner Tx)

Not used

Ch
1

Ch
0

Channel state

Where: 0 = off, 1 = on