Calibrate the analog current output module, Important – Rockwell Automation 1734-XXXX POINT I/O Digital and Analog Modules and POINTBlock I/O Modules User Manual

Page 123

Advertising
background image

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013

Calibrate Your Analog Modules 125

Calibrate the Analog
Current Output Module

To calibrate your output module, connect the module in a DeviceNet system
similar to that shown in the figure, and use this procedure.

1. Double-click the icon to bring up the General parameter dialog.

You see the EDS editor ask you if you want to upload the configuration
from the device.

IMPORTANT

Apply power to the power supply and module for at least
10 minutes before calibrating the module. This allows
internal temperatures to stabilize and reduces drift errors.

0

1

0

1

0

1

0

1

0

1

0

1

44032

Power Supply Voltage

DeviceNet Input

PDN OE2C

250

Ω

Current Meter

Channel 0
Connect to 0 and 4

Channel 1
Connect to 1 and 5