Rockwell Automation Publication 1734-UM001E-EN-P - July 2013

Troubleshoot with the Indicators 153

Indication

Probable Cause

Recommended Action

POINTBus Status

Off

Device not powered - check module status indicator.

Apply power to device.

Alternating red/green

LED power cycle test is present.

None.

Flashing red

Recoverable fault has occurred:

At power up the number of expected modules does not equal the number of

modules present

A module is missing

Node fault (I/O connection timeout)

Change chassis size to match number of

modules present.

Replace missing module.

Check for I/O Module failure and correct, as

needed.

Flashing green

Adapter online with no connections established.

Adapter chassis size has not been configured

Controller in program/idle mode

ControlNet cable break

Firmware (NVS) update


Set adapter chassis size.

None.

Check cable and connect, as needed.

Complete firmware update.

Solid green

Adapter online with connections established (normal operation, in run mode) None.

Solid red

Unrecoverable fault occurred - the adapter is bus off.

1. Cycle power to device.
2. If condition persists, replace device.

Indication

Probable Cause

Recommended Action

ControlNet A/B Status

Viewed Together (A and B)

Both Steady Off

Reset, no power, or entire network interface deactivated.

None or cycle power.

Alternating red/green Self test mode is present.

None.

Alternating red/Off

Incorrect configuration is present.

Check network address and other ControlNet
configuration parameters.

Both Steady red

Faulted unit is present.

Cycle power or reset unit. If fault persists, contact
A-B representative or distributor.

Viewed Individually (A or B)

Steady Off

Channel disabled.

Program network for redundant media, if required.

Flashing red/green

Incorrect network configuration is present.

Cycle power or reset unit. If fault persists, contact
A-B representative or distributor.

Flashing red/Off

Media fault.

No other nodes present on network.

Check media for items such as broken cables,

loose connectors, and missing terminators.

Add other nodes to the network.

Flashing green/Off

Temporary channel errors are present.

Node is not configured to go on line.

Make sure the configuration manager node is
present and working and selected address is not
greater than selected UMAX.

(1)

Steady green

Normal operation - MAC frames are being received without detected errors.

None.

(1) The configuration manager node is the node responsible for distributing ControlNet configuration data to all nodes on the network.