Troubleshoot with the Indicators 157

Indication

Probable Cause

Recommended Action

System Power

Off

Not active; field power is off or DC-DC converter problem present. 1. Verify power is on, and apply power if needed.

2. Verify backplane power not exceeded, and correct, as
needed.
3. Replace 1734-AENT module.

Green

System power is on; DC-DC converter is active (5V).

None.

Field Power

Off

Not active; field power is off.

Apply field power.

Green

Power is on; 24V is present.

None.

Indication

Probable Cause

Recommended Action

Network Activity

Off

No link established.

Verify network cabling, and correct, as needed.

Flashing green/Off

Transmit or receive activity present.

None.

Steady green

Link established.

None.

Network Status

Off

Device not initialized. The module does not have an IP address.

Apply power to device, verify IP address, and
correct, as needed.

Flashing green

No CIP connections present. Device has an IP address, but no CIP connections are
established.

None.

Solid green

CIP connections present. Device online and has an IP address, and CIP
connections are established.

None.

Flashing red

One or more CIP connections has timed-out.

Check for I/O module failure and controller
operation, and correct, as needed.

Solid red

Duplicate IP address detected.

Verify IP address setting and correct, as needed.

Flashing red/green

The module is performing a self-test (only occurs during power cycle test).

None.