Work with alarm configuration dialog – Rockwell Automation 1734-XXXX POINT I/O Digital and Analog Modules and POINTBlock I/O Modules User Manual

Page 190

Advertising
background image

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013

198 Configure POINT I/O Modules in RSLogix 5000 Software

See the figure that shows configuration parameters for each channel in
individual rows on the grid with, for example, 1734-OE2C having two
output channels.

2. From the Configuration dialog, complete entries, referring to the table.

3. From the bottom of the Configuration dialog, perform one of the

following:

Click another tab at the top of the dialog.
or

Click OK to save changes and close the dialog.
or

Click Cancel to return to default values.
or

Click Apply to save changes you made on any of the dialogs and
continue to display the dialog, noting that you enable the Apply button
when you make changes to any of the dialogs.

Work with Alarm Configuration Dialog

This dialog does not appear for Listen Only connections. To complete the entries
on this dialog, proceed as follows.

For This Value

Select

Comments

High Engineering

-32768…32767

Default for 1734-OE2C analog output module is 8191.
Default for 1734-OE2V analog output module is 10000.

Low Engineering

-32768…32767

Default for 1734-OE2C analog output module is 1638.
Default for 1734-OE2V analog output module is 0.

Current Range

4…20 mA
0…20 mA

Default is 4…20 mA.

Voltage Range

-10…10V
0…10V

Default is 0…10V