1734-ow2 and 1734-ow4 relay output modules – Rockwell Automation 1734-XXXX POINT I/O Digital and Analog Modules and POINTBlock I/O Modules User Manual

Page 42

Advertising
background image

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013

26 Install POINT I/O Modules

1734-OW2 and 1734-OW4 Relay Output Modules

1734-OW2 Modules with Load Powered by Internal Power Bus
Wiring Diagram

ATTENTION: Relay contacts are not powered by the internal power bus.
Load power can be provided by the internal power bus or an external
power source.

Channel

Output

Common

Supply

0A

0

4

6

0B

2

4

6

1A

1

5

7

1B

3

5

7

Supply voltage can range from +5V DC…240V AC, depending on relay load.
Power for the module can be provided by the internal power bus.

Relay

Output

Module

Status

Network

Status

1734

OW2

NODE:

0

1

41974

Module Status

Network Status

Status of Output 0

Status of Output 1

C

V

C

V

C = Common
V = Supply

Output 0A

Output 0B

Output 1A

Output 1B

Output 0A

Output 0B

Output 1A

Output 1B

Output 2A

Output 2B

Output 3A

Output 3B

Relay

Output

Module

Status

Network

Status

1734

OW4

NODE:

0

1

2

3

1734-OW4

1734-OW2

Status of Output 0

Status of Output 1

Status of Output 2

Status of Output 3

Module Status

Network Status

C

C

V

V

Out = Output channel relay contacts
V = Supply (can range from +5V DC…240V AC)
C = Common

Out 0A

Out 0B

Out 1A

Out 1B

Load

Load

0

2

4

6

3

5

7

1

Advertising