Rockwell Automation 1734-XXXX POINT I/O Digital and Analog Modules and POINTBlock I/O Modules User Manual

Page 94

Advertising
background image

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013

96 POINT I/O Module Data

Default Data Map for the 1734-IB2 and 1734-IV2 Input Modules

Message Size: 1 Byte

7

6

5

4

3

2

1

0

Produces (scanner Rx)

Not used

Ch1

Ch0

Consumes (scanner Tx)

No consumed data

Where: Ch0 = input channel 0, Ch1 = input channel 1, 0 = off, 1 = on

Default Data Map for the 1734-IB4 and 1734-IV4 Input Modules

Message Size: 1 Byte

7

6

5

4

3

2

1

0

Produces (scanner Rx)

Not used

Ch3

Ch2

Ch1

Ch0

Consumes (scanner Tx)

No consumed data

Where: Ch0 = input channel 0, Ch1 = input channel 1, Ch2 = input channel 2, Ch3 = input channel 3, 0 = off, 1 = on

Default Data Map for the 1734-IB8 and 1734-IV8 Input Modules

Message Size: 1 Byte

7

6

5

4

3

2

1

0

Produces (scanner Rx)

Ch7

Ch6

Ch5

Ch4

Ch3

Ch2

Ch1

Ch0

Consumes (scanner Tx)

No consumed data

Where: Ch0 = input channel 0, Ch1 = input channel 1, Ch2 = input channel 2, Ch3 = channel 3, Ch4 = input channel 4, Ch5 = input channel
5, Ch6 = input channel 6, Ch7 = input channel 7, 0 = off, 1 = on

Default Data Map for 1734-IB4D Module - Produced Assembly Instance 101

Message Size: 2 Bytes

7

6

5

4

3

2

1

0

Produce 0 (Rx)

Fault 3

Fault 2

Fault 1

Fault 0

Input 3

Input 2

Input 1

Input 0

Produce 1 (Rx)

SC 3

SC 2

SC 1

SC 0

OW 3

OW 2

OW 1

OW 0

Consume (Tx)

No consumed data

Where: OW = open wire, SC = short circuit, fault = open wire or short circuit.

Default Data Map for 1734-IB4D Module - Produced Assembly Instance 23

Message Size: 1 Byte

7

6

5

4

3

2

1

0

Produce 0 (Rx)

Fault 3

Fault 2

Fault 1

Fault 0

Input 3

Input 2

Input 1

Input 0

Consume (Tx)

No consumed data

Where: Fault = open wire or short circuit.