Input modules, Output modules, Input modules output modules – Rockwell Automation 1734-XXXX POINT I/O Digital and Analog Modules and POINTBlock I/O Modules User Manual

Page 18

Advertising
background image

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013

2 About the Modules

Input Modules

For input modules, DC inputs are 24V DC nominal, with an input range of
10…28.8V dc, and are offered with 2, 4,or 8 sinking style inputs, or 2, 4, or 8
sourcing style inputs. The 1734-IB2, 1734-IB4, 1734-IB4D, and 1734-IB8 input
modules are sinking modules. The 1734-IV2, 1734-IV4, and 1734-IV8 modules
are sourcing input modules.

For input modules, AC inputs are 120V AC nominal with an input range of
85…132V ac, or 220V AC nominal with an input range of 159…264V ac, with
sinking inputs.

Features of the all input modules include the following:

Autobaud (will match baud of existing devices on the network)

Selectable input filter times (0…65 ms with 1 ms default)

Sequential auto addressing

Output Modules

T

he 1734-OB2, 1734-OB4, 1734-OB8, 1734-OB2E, 1734-OB4E, and 1734-

OB8E DC output modules have current limited sourcing outputs, which source a
positive voltage of up to 1 A with respect to their DC return per channel. The
1734-OB2EP sources a positive voltage of up to 2 A with respect to its DC
return per channel. The outputs are not isolated from each other. For these
modules, DC outputs are 24V DC nominal, with a range of 10…28.8V dc. A
number of output diagnostic features are incorporated to assist in
troubleshooting

. The 1734-OB2E, 1734-OB2EP, 1734-OB4E, and 1734-OB8E

modules feature the following:

Output diagnostics (short circuit and wire-off indication and reporting
bits per channel)

Current limited outputs

Autobaud (will match baud of existing devices on the network)

Sequential auto addressing

The 1734-OV2E, 1734-OV4E, and 1734-OV8E modules are protected sink
output modules protected to 1 A. The outputs are not isolated from each other.
For these modules, DC outputs are 24V DC nominal, with a range of 10…28.8V
dc. A number of output diagnostic features are incorporated to assist in
troubleshooting

. The 1734-OV2E, 1734-OV4E, and 1734-OV8E modules

feature the following (note that 1734-OV2E, 1734-OV4E, and 1734-OV8E
modules have no wire-off indication):

Output diagnostics (short circuit and reporting bits per channel)

Current limited outputs

Autobaud (will match baud of existing devices on the network)

Sequential auto addressing