Chapter

6

Troubleshoot with the Indicators

About This Chapter

Read this chapter for information about troubleshooting with the following
indicators:

Module status

Network status

Power indication

Calibration status

I/O POINT status (ON/OFF/fault or diagnostic)

Refer to each module’s individual indicators for detailed information.

About Module Diagnostics

All status and diagnostic information (strobed, polled, cyclic, or change-of-state)
is reported back over the network communication adapter. A single point of
failure is detected and reported at the module and to the control system.

24VDC

Sink

Input

Module

Status

Network

Status

1734

IB4

NODE:

0

1

2

3

Node-level Diagnostics:

Point-level Diagnostics:

·

Module Status Indicator
indicates the health of the
module

·

Network Status Indicator

indicates the health of the
POINTBus or backplane

·

I/O Point Indicator

indicates I/O (ON/OFF or fault/
diagnostic) status

·

Digital outputs
Short circuit for ON-state
Open circuit for OFF-state

·

Analog I/O
Loss of field power
Open wire
Calibration status

I/O Channel Status

Module Status

Network Status