Rockwell Automation Publication 1734-UM001E-EN-P - July 2013

Configure POINT I/O Modules in RSLogix 5000 Software 187

1. From the General dialog, select Fault/Program Action.

You see the Fault/Program Action dialog. See the figure for the Fault/
Program Action dialog for an 8-point output module. The dialogs for 2-
point and 4-point output modules are identical except for the number of
point you can configure. Use this dialog to configure the Program mode
and Fault mode for channels for the following modules:

Without diagnostic status

With overload diagnostic status

With overload and open load diagnostic status

2. From the Fault/Program Action dialog, complete entries, referring to the

table for a summary of how to make these entries.

3. From the Fault/Program Action dialog, perform one of the following:

Feature

Description

Point

Displays the channel numbers.

Program
Mode

Select a value to determine the behavior of each output when the

controller transitions to the Program mode.

Make a selection from the available values for each channel:

- Off (default)
- On
- Hold

In Hard Run only, you disable editing this feature.

Fault Mode

Select a value to determine the behavior of each output when

communication with the controller fails.

Select from the available values for each channel:

- Off (default)
- On
- Hold

In Hard Run only, you disable editing this feature.