Remove a mounting base – Rockwell Automation 1734-XXXX POINT I/O Digital and Analog Modules and POINTBlock I/O Modules User Manual

Page 29

Advertising
background image

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013

Install POINT I/O Modules 13

2. Rotate the terminal block into the mounting base until it locks itself in

place.

3. If an I/O module is installed, snap the RTB handle into place on the

module.

Remove a Mounting Base

To remove a mounting base, you must remove any installed module, and remove
the removable terminal block (RTB), if wired.

1. Unlatch the RTB handle on the I/O module.
2. Pull on the RTB handle to remove the RTB.
3. Press in on the module lock on the top of the module, and pull up on the

I/O module to remove it from the base.

4. Remove the module to the right of the base you are removing, noting that

the interlocking portion of the base sits under the adjacent module.

5. Use a small-bladed screwdriver to rotate the orange DIN-rail locking screw

on the mounting base to a vertical position, noting that this releases the
locking mechanism.

6. Lift the mounting base straight up to remove.

WARNING: When you insert or remove the module while backplane
power is on, an electrical arc can occur. This could cause an explosion in
hazardous location installations. Be sure to remove power or that the
area is nonhazardous before proceeding.