Rockwell Automation 1734-XXXX POINT I/O Digital and Analog Modules and POINTBlock I/O Modules User Manual

Page 194

Advertising
background image

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013

202 Configure POINT I/O Modules in RSLogix 5000 Software

You see a Low Value dialog.

6. From the Low Value dialog, follow the instructions you see and click Next.

You see the High Value dialog.

7. From the High Value dialog, follow the instructions you see and click Next

to start calibration.

8. If calibration completes successfully, you see the Calibration Completed

dialog.