Rockwell Automation Publication 1734-UM001E-EN-P - July 2013

POINT I/O Module Data 113

clamped. The clamps are absolute. Regardless of what is sent to the module or
what the fault state values are, the module does not operate outside these settings.

Latch Alarms

The latched alarms let low and high clamp status information to be latched. If an
output is clamped momentarily, the clamp status bit stays set until a reset latch
service is issued. The default setting is Unlatched. Each channel can be
configured individually. You can enable the Latch on a per-channel basis.

Alarm Disable

This function disables all channel alarms and faults so they are not reported in
the channel status field. The channel LED status indicator stays solid green, and
Latch Alarms are ignored. Change-of-state has no effect on module behavior.
Default state is Alarms Enabled. Each channel can be configured individually.
You can disable Alarms on a per-channel basis or they can be set with the Module
Configuration Assembly.

Channel Indicators

See the table for channel indicator states for given module condition.

Indication

1734-OE2C Probable Cause

1734-OE2V Probable Cause

Channel Status

Off

Module in CAL mode

Module in CAL mode

Solid green

Channel actively controlling
outputs

Channel actively controlling
outputs

Blinking green

Channel calibrating

Channel calibrating

Blinking red

Open wire or no power

Low/High Clamp alarm

Solid red

Unrecoverable fault - may require
device replacement

Loss of field power